GCS High and low voltage draw out switchgear

Products Details

Overview

GCS low-voltage withdrawable switchgear is suitable for power distribution systems in power plants, petroleum, chemical, metallurgy, textile, high-rise buildings and other industries. In large power plants, petrochemical systems and other places with a high degree of automation and requiring interface with computers, it can be used as a power generation and power supply system with a three-phase AC frequency of 50 (60) Hz, a rated working voltage of 400V, 660V, and a rated current of 5000A and below. A low-voltage complete set of power distribution devices used in power distribution, motor centralized control, and reactive power compensation. The design of the device complies with the following standards: IEC439-1 "Low-voltage switchgear and control equipment" GB7251 "Low-voltage switchgear".

Model Meaning

P-D-1

Normal use environment

◆The ambient air temperature should not be higher than +40℃, not lower than -5℃, and the average temperature within 24 hours should not be higher than +35℃. When it exceeds, the derating operation shall be performed according to the actual situation; ◆For indoor use, the altitude of the place of use shall not exceed 2000m; ◆The relative humidity of the surrounding air does not exceed 50% when the maximum temperature is +40°C, and a relatively large relative humidity is allowed at a lower temperature, such as 90% at +20°C. produce condensation effects; ◆When the device is installed, the inclination of the vertical plane should not exceed 5°, and the entire group of cabinets should be relatively flat (in line with GBJ232-82 standard); ◆The device should be installed in a place without severe vibration and shock and not enough to cause the electrical components to be corroded; ◆When users have special requirements, they can negotiate with the manufacturer.

The main technical parameters

Serial number

Rated current (A)

Parameter

1

Main circuit rated voltage (V)

AC 400/660

2

Auxiliary circuit rated voltage

AC 220, 380 (400), DC 110, 220

3

Rated frequency(Hz)

50(60)

4

Rated insulation voltage (V)

660

5

Rated current (A)

Horizontal busbar

≤5000

Vertical Busbar (MCC)

1000

6

Busbar rated peak withstand current (KA/0.1s)

50.8

7

Busbar rated peak withstand current (KA/0.1s)

105,176

8

Power frequency test voltage (V/1min)

The main circuit

2500

Auxiliary circuit

2000

9

busbar

Three-phase four-wire system

A.B.C.PEN

Three-phase five-wire system

A.B.C.PE.N

10

Protection class

IP30.IP40