Description
under lower temperature. For example, RH could be 90% at +20℃, special measures should be taken to occurrence of dews; Pollution degree: 3 Installation category: Ⅲ Installation conditions : the inclination between installation plane and vertical plane is within ± 5 ° Impact and shake: the products should locate in the places where there are no obvious impact and shake.Technical Specification
Standard | IEC/EN60947-4-1 | ||||||
Model No. | CJ19-25 | CJ19-32 | CJ19-43 | CJ19-63 | CJ19-80 | CJ19-95 | |
Rated Conventional Heating Current | Ith (A) | 25 | 32 | 43 | 63 | 80 | 95 |
Rated Work Current | 415V/Ie (A) | 18 | 25 | 32 | 60 | 80 | 95 |
Capacitor Controlled | 220V/240V(Kvar) | 6 | 9 | 10 | 15 | 18 | 22 |
400V/440V(Kvar) | 12 | 18 | 20 | 30 | 36 | 40 | |
Rated Insulation Voltage | Ui(V) | 690 | 690 | 690 | 690 | 690 | 690 |
Rated Operation Voltage Electrial life(x103 ) | Ue(V) | 400 | 400 | 400 | 400 | 400 | 400 |
Times | 120 | 120 | 120 | 100 | 100 | 100 | |
Mechanical life(x103 ) | Times | 3000 | 3000 | 3000 | 3000 | 3000 | 3000 |
Restrained Surge Capacity | x Ie | 15 | |||||
Auxiliary Contact | Ith=10A | AC-15 360VA;DC-13 33W | |||||
Control Capacity |
Coil Parameters
Coil Power(VA) | Start-up | 76 | 110 | 110 | 230 | 230 | 230 |
Holding | 10 | 11 | 11 | 32 | 32 | 32 | |
Rated Control Power | Us(V) | 24,36,48,110,220,380 | |||||
Pull time | Ms | 12~22 | 15~24 | 15~24 | 20~26 | 20~35 | 20~35 |
Release time | Ms | 4~12 | 5~19 | 5~19 | 8~12 | 6~20 | 6~20 |
Operation Range | Pick-up | (85%-110%)Us | |||||
Drop-out | (20%-75%)Us |
Model | Amax | Bmax | Cmax | Dmax | E | F | Note |
CJ19-25 | 80 | 47 | 124 | 76 | 34/35 | 50/60 | be fixed with 35mm din rail |
CJ19-32 | 90 | 58 | 132 | 86 | 40 | 48 | |
CJ19-43 | 90 | 58 | 136 | 86 | 40 | 48 | |
CJ19-63 | 132 | 79 | 150 | - | - | - | Not only fixed by screws but also could be fixed with 35mm and 75mm din rail |
CJ19-80~95 | 135 | 87 | 158 | - | - | - |